NEW 80kW MAN Natural Gas Gensets & CHPs (50Hz Applications) HTG-80GF Rated power 80kW
Standby power 88kW
Engine Model MAN / E0836LE302 Rated Power/ Standby Power 110kW
Rotation Speed (RPM) 1500
Fuel consumption at 100% load, 0.3 m³/kW·h
Rated Voltage: generally the rated power includes 380/220V, 400/230V, 415/240V, 440/254V, we make it according to client's
requirements.
HAITAI MAN series gas gensets & CHPs are driven by MAN engines originally
made in Germany, one of the world top engine brands all over the world.
This series generator sets choose high quality natural gas engine assembled with alternators
(Stamford, Faraday or other famous brand), the control system adopts PLC automatic controller.
Advantages of MAN Natural Methane Gas Generator Set Reliable service life resulting from application-specific design
Powerful to ensure uninterrupted operation
Adapt to harsh conditions
Applications of Natural Methane Gas Generator Set
High reliable and outstanding performance due to field-tested technology
The engine design is based on continuous working of 24 hours per day, 7 days per week
High Power and maximum efficiency, the best ideal engine for applications of CHP, CCHP, Cogeneration and
distribution energy system
Low operating cost as a result of low levels of lubricant and fuel consumption, as well as extended service intervals(component stability)
Low emissions due to state-of-the-art combustion technologies
Low space requirements due to compact design
Long service life resulting from application-specific-design and tailored machinery-configuration
MAN Engine Overhaul Time is around 65000 hours.
ISO9001 and CE approval.
Pipeline Natural Gas (PNG, CNG, LNG), Oilfield APG (Associated Petroleum Gas), Coalmine Methane Gas, CBM (Coalbed Methane), Well Gas, Shale Gas & Other Methane Based Gases, Gas Fuel Quality Requirements
ADDITIONAL FEATURES Customisable status screens.
Multiple date & time scheduler.
Charge alternator failure alarm.
CAN engine manual speed control.
Manual fuel pump control.
Engine exerciser.kW & kV Ar overload protection.
Reverse power (kW & kV Ar) protection. Unbalanced load protection.
USB connectivity.
Backed-up real time clock.
Configurable Gencomm pages.
SMS messaging start & stop functionality.
Modem diagnostic display screens.
Remote display support (max 3 units)
Control PanelThe DSE7310 is an Auto Start Control Module and the DSE7320 is an Auto
Mains (Utility) Failure Control Module suitable for a wide variety of single,
diesel or gas,gen-set applications
Attachment (Optional Parts) 20ft Container canopy Scientific and efficient Special sand-proof waterproof blinds with illumination.
Soundproof Canopy (Super Silent canopy)Containerized Canopy
CHP system (Exhaust Heat Collector) Cogeneration Automatic Paralleling and Gridconnect Control SystemThis system can connect generator sets in parallel or connect the generator set to the grid automatically.
CCHP/Trigeneration
Remote Control
PMG Alternator
Oil and Water Heater
High Voltage Alternator 6.3kv and 10.5kv, High Voltage Electrical Control Cells (PT Cabinet
CT Cabinet
High Voltage outgoing cabinet
DC Panel, Groud Resistance Cabinet and low voltage distribution cabinet etc)
Lubrication system Daily auxiliary oil tank
Auto refilling oil system
Electrical system RCD
ATS control cabinet
Thermal power gauge, Electric power gauge
Sync paralleling control system
Gas supply system
Gas flow gauge
Emergency pressure relief torch Water separator
Gas compressor
G
as purification device
Remarks: Both 50Hz and 60Hz are available.
Special voltages available.
Alternator brand Stamford,Leroy Somer,Marathon are optional.
Controller brand Deepsea,Comap are optional.
Special requirements for Soundproof Canopy, ATS, Parallel & Synchronization Control, CHP and Biogas Pre-treatment Machinery are optional
The data herein can vary depending on individual production
Sea-Level<1000m , Temp<40deg.
The specification of the 80kW MAN Natural Gas Gensets HTG-80GF
50Hz Applications
Genset Model MAN HTG-80GF
Engine Model MAN / E0836LE302
Rated Power/ Standby Power 110kW
Engine Type In-line, Four Stroke
Rated Speed 1500 rpm
Cylinder No. 6 In- line
Bore ×Stroke 108×125mm
Start Method Electric
Air-fuel Ratio 11:1
Crankshaft Rotation Direction Inverse Hour (From Flywheel)
Cooling Method Liquid
Aspiration Type Turbocharged
Speed Governor Electronic
Gas Mixer Formation Pre-Mix
Displacement 6.87 L
Thermal Efficiency 47.6%
Mechanical Efficiency 41.9%
Total Efficiency 89.5%
Emissions status NOx <500 mg/Nm3
Standby power 110kW Power factor 0.8
Excitation Type Brushless Insulation class Class H
Connection 3-pahse, 4-wire
Cooling Air cooled
Protection Class IP23
Voltage Regulation Mode AVR (Automatic)
Electrical performance
Voltage setting range: ≥+-5%
Steady-state voltage regulation: ≤+-1%
Transient voltage deviation(100% Sudden power reduction) ≤+25%
Transient voltage deviation(Sudden power plus) ≤-20%
Voltage stabilization time(100%Sudden power reduction) ≤6S
Voltage stabilization time (Sudden power plus) ≤6S
Steady - state frequency regulation ≤5%
Frequency fluctuation rate ≤1.5%
Transient frequency deviation (100% Sudden power reduction) ≤+12%
Transient frequency deviation (Sudden power plus) ≤-10%
Frequency recovery time (100% Sudden power reduction) ≤5S
Frequency recovery time (Sudden power plus) ≤5S
Approximated Dimensions & Weigh
L x W x H: 3700x1150x1700 (mm)
Gross Weight: 2200 kg